SES-1200-XXX
Advantages & Functions
- Modular system
- Variable siren signals with DSP (Digital Signal Processing)
- Extremely high efficiency dB/W
- Power control of the siren signal
- Compensation of changes in battery voltage and loudspeaker impedance
- Short-circuit proof
- Overtemperature monitoring
- Silent test of loudspeaker systems
- Automatic system test
- Status displays
- Microprocessor-controlled function monitoring by system
- Service program for on-site diagnosis
- Two batteries
- Output power is 600 W True RMS per amplifier, corresponds to 1200 W True RMS
Technical details
General | ||
Sound pressure level in dB(A) at a distance of 30 m | 113 - 122dB(A) | |
Base frequency | 415 Hz | |
Number of acoustic radiators | 8 | |
Air Humidity | 0% - 100% | |
Acoustic radiators | ||
Acoustic radiators made of | Material ALSi7Mg0,35F - seawater resistant aluminium alloy | |
Temperature range | -50°C to+ 70°C | |
Set of screws | V2A | |
Total weight | 68,6 - 85,1 kg | |
Dimensions (W x H x D) | 180°: 830 x 2666 x 160 mm 360°: 830 x 1590 x 830 mm 0°: 630 x 2666 x 280 mm | |
Control unit | ||
Number of power amplifiers | 2 | |
Power output RMS | 1200 W | |
Mains voltage | 230 VAC | |
Power consumption in standby mode | 3,5 VA | |
Power consumption during battery charging | 93 W | |
Number of potential free inputs | 3 | |
Number of potential free outputs | optional 2 potential-free outputs for sum fault and alarm active max. 24 V / 100 mA | |
Status identification via service interface | all status messages can be displayed via a service program at the service interface | |
Battery voltage / capacity (C20) | 24 V / 55 Ah | |
Battery capacity | 24 days with 20 alarms of 1 min. each | |
Temperature range electronics | -40°C to+ 70°C | |
Temperature range batteries | -25°C to+ 60°C | |
Type of protection | IP 66 | |
Cabinet dimenstions (W x H x D) | 600 x 600 x 300 mm | |
Weight | 87 kg | |
Color | RAL 7035 |